Powermonitor 3000 Master Module 47
Publication 1404-IN007F-EN-P - November 2009
The 1786-CP cable can be plugged into any ControlNet product’s NAP to provide
programming capability on the ControlNet network. A programming terminal connected
through this cable is counted as a node and must have a unique network address.
Interpret the Status Indicators
The power monitor is equipped with six bi-color status indicators.
The three status indicators on the left display the same information on power monitor
modules with any communication option including native RS-485 communication only. The
three status indicators on the right have different labels and different indications depending
on the communication option selected, as shown in these charts.
ATTENTION
Use a 1786-CP cable when connecting a programming terminal to the network through
NAPs. Using a commercially available RJ-style cable could result in network failure.